Detail Electronic Expansion Valve EX4-EX8 Emerson
EX4-EX8 Electrical Control Valve ( R-410A)
Features
• Fully hermetic design
• Fast full stroke time
• Applicable to all common refrigerants ( HCFC, HFC) , for
subcritical CO2 applications
• High resolution and excellent repeatability
• Bi-flow versions for heat pump applications
• Positive shut-off function to eliminate the use of an
additional solenoid valve
• Linear flow capacity
• Wide capacity range ( 10 - 100% )
• Continuous modulation of mass flow, no stress
( liquid hammering) in the refrigeration circuit
• Direct coupling of motor and valve for high reliability
( no gear mechanism)
• Ceramic slide and port for accurate flow and minimal wear
• Balanced force design
• Corrosion resistant stainless steel body, and connections
Specifications
• CE marking: EX4/ EX5: not required
EX6-EX8: required, Cat I, Module A
• MOPD: EX4-EX6: 580 psid, EX7-EX8: 435 psid
• MWP: 650 psig
• Ambient temperature: -40° F to + 130° F
• Humidity: 5 to 95% R.H.
• External leakage: d 0.1 oz/ yr ( R-22)
• Stepper motor type: Bi-polar, phase current by
chopper control
( constant current)
• Electrical connection: 4 pin terminal via plug
• Driver supply voltage: Recommended: 24 VDC
Range: 18-36 VDC
• Phase current ( operating) : EX4-EX6: 500 mA max
EX7: 750 mA
EX8: 800 mA
• Holding current: EX4-EX6: 100 mA
EX7: 250 mA
EX8: 500 mA
• Nominal input power
per phase: EX4-EX6: 3.5W
EX7-EX8: 5W
• Phase inductance: EX4-EX6: 30 mH ± 25%
EX7: 20 mH ± 25%
EX8: 22 mH ± 25%
• Step mode: 2 phase full step
• Step angle: 1.8° per step ± 8%
• Total number of steps: EX4-EX6: 750 full steps
EX7: 1600 full steps
EX8: 2600 full steps
• Stepping rate: 500 Hz
• Winding resistance
per phase: EX4-EX6: 13 ohm ± 10%
EX7: 8 ohm ± 10%
EX8: 6 ohm ± 10%
• Full travel time: EX4-EX6: 1.5 seconds
EX7: 3.2 seconds
EX8: 5.2 seconds
Tampilkan Lebih Banyak